LC1F150 Contactor 4-29-00-0273
TeSys F contactor, 3 poles (3NO), 150A/690V AC-3, for motor applications up to 75kW@400V. Contactor with no coil to allow a later selection and installation (coil to be ordered separately), it provides bolt terminals for bars or cables with lugs. For high operating rates until 2400 cycles/hour and environments until 55°C, it procures high reliability and durability. It makes installation and maintenance easy thanks to a drawer for insertion of the selected coil and a large choice of add-on blocks and accessories (to be ordered separately). Multi standards certified (IEC, UL, CSA, CCC, EAC, Marine), Green Premium compliant (RoHS/REACh).
- Range:
- Product Name:
- Product or Component Type:
- Device Short Name:
- Contactor Application:
- Resistive load
- Motor control
- Utilisation Category:
- Poles Description:
- Power Pole Contact Composition:
- [Ue] Rated Operational Voltage:
- <= 690 V AC 50/60 Hz
- <= 460 V DC
- [Ie] Rated Operational Current:
- 250 A (at <40 °C) at <= 440 V AC-1
- 150 A (at <55 °C) at <= 440 V AC-3
- Motor Power (kW):
- 75 kW at 380...400 V AC 50/60 Hz (AC-3)
- 80 kW at 415 V AC 50/60 Hz (AC-3)
- 80 kW at 440 V AC 50/60 Hz (AC-3)
- 90 kW at 500 V AC 50/60 Hz (AC-3)
- 40 kW at 220...240 V AC 50/60 Hz (AC-3)
- 100 kW at 660...690 V AC 50/60 Hz (AC-3)
- 22 kW at 400 V AC 50/60 Hz (AC-4)
- Complementary:
- [Uc] Control Circuit Voltage:
- 24...575 V AC 40...400 Hz with LX1/LX9 coil
- 24...460 V DC with LX4 coil
- 100...250 V AC 50/60 Hz with LXE coil
- 100...380 V DC with LXE coil
- [Uimp] Rated Impulse Withstand Voltage: 8 kV
- Overvoltage Category: III
- [Ith] Conventional Free Air Thermal Current: 250 A (at 40 °C)
- Irms Rated Making Capacity: 1500 A conforming to IEC 60947-4-1
- Rated Breaking Capacity: 1200 A conforming to IEC 60947-4-1
- [Icw] Rated Short-Time Withstand Current:
- 1200 A at 40 °C for 10 s
- 700 A at 40 °C for 30 s
- 600 A at 40 °C for 1 min
- 450 A at 40 °C for 3 min
- 350 A at 40 °C for 10 min
- Associated Fuse Rating:
- 160 A aM at <= 440 V
- 250 A gG at <= 440 V
- Average Impedance: 0.35 mOhm at Ith 250 A 50 Hz
- [Ui] Rated Insulation Voltage:
- 1000 V conforming to IEC 60947-4-1
- 1500 V conforming to VDE 0110 group C
- Power Dissipation Per Pole:
- Control Circuit Voltage Limits:
- Operational: 0.85...1.1 Uc AC 40...400 Hz with LX1/LX9 coil
- Drop-out: 0.2...0.55 Uc AC 40...400 Hz with LX1/LX9 coil
- Operational: 0.85...1.1 Uc DC with LX4 coil
- Drop-out: 0.15...0.2 Uc DC with LX4 coil
- Operational: 85...275 V AC 50/60 Hz with LXE coil
- Drop-out: 0...60 V AC 50/60 Hz with LXE coil
- Operational: 85...418 V DC with LXE coil
- Drop-out: 0...45 V DC with LXE coil
- Heat Dissipation: 5.9…7.2 W, 2.2…2.5 W
- Operating Time:
- 35 ms closing with LX1/LX9 coil
- 130 ms opening with LX1/LX9 coil
- 30...40 ms closing with LX4 coil
- 30...50 ms opening with LX4 coil
- 40...80 ms closing with LXE coil
- 6...54 ms opening with LXE coil
- Mounting Support: Plate
- Standards:
- IEC 60947-4-1
- EN 60947-4-1
- IEC 60947-1
- EN 60947-1
- JIS C8201-4-1
- Product Certifications:
- RINA
- CSA
- BV
- RMRoS
- LROS (Lloyds Register of Shipping)
- DNV
- ABS
- UL
- CB
- UKCA
- Connections - Terminals:
- Power circuit:
- Lugs-ring terminals 1 cable(s) 120 mm² - busbar cross section: 25 x 3 mm
- Connector 1 cable(s) 120 mm²
- Bar 2 cable(s)
- Bolted connection
- Control circuit:
- Screw clamp terminals 1 cable(s) 1…4 mm² flexible without cable end
- Screw clamp terminals 2 cable(s) 1…4 mm² flexible with cable end
- Screw clamp terminals 1 cable(s) 1…4 mm² flexible with cable end
- Screw clamp terminals 2 cable(s) 1…2.5 mm² solid without cable end
- Screw clamp terminals 1 cable(s) 1…4 mm²
- Screw clamp terminals 2 cable(s) 1…4 mm²
- Screw clamp terminals 1.0 cable(s) 0.2…2.5 mm² flexible without cable end
- Screw clamp terminals 1.0 cable(s) 0.25…2.5 mm² flexible with cable end
- Screw clamp terminals 1.0 cable(s) 0.2…2.5 mm² solid without cable end
- Tightening Torque:
- Power circuit: 18 N.m
- Control circuit: 1.2 N.m, 0.6 N.m
- Mechanical Durability: 10 million cycles
- Inrush Power in VA:
- 690…855 VA, 40...400 Hz cos phi 0.9 (at 20 °C) with LX1/LX9 coil
- 543…665 VA (at 20 °C) with LX4 coil
- 280…310 VA, 50/60 Hz cos phi 0.5 (at 20 °C) with LXE coil
- 270…320 VA (at 20 °C) with LXE coil
- Hold-in Power Consumption in VA:
- 6.6…8.1 VA, 40...400 Hz cos phi 0.9 (at 20 °C) with LX1/LX9 coil
- 3.94…4.83 VA (at 20 °C) with LX4 coil
- 4.5…7.0 VA, 50/60 Hz cos phi 0.5 (at 20 °C) with LXE coil
- 2.5…4.0 VA (at 20 °C) with LXE coil
- Maximum Operating Rate: 2400 cyc/h at 55 °C
- Compatibility Code: LC1F
- Environment:
- IP Degree of Protection:
- IP2X front face with shrouds conforming to IEC 60529
- IP2X front face with shrouds conforming to VDE 0106
- Protective Treatment: TH
- Ambient Air Temperature for Operation: -40…60 °C
- Ambient Air Temperature for Storage: -60…80 °C
- Permissible Ambient Air Temperature Around the Device: 60…70 °C at Uc
- Operating Altitude: 3000 m without derating
- Mechanical Robustness:
- Vibrations contactor open: 2 Gn, 5...300 Hz
- Vibrations contactor closed: 6 Gn, 5...300 Hz
- Shocks contactor open: 9 Gn for 1/2 sine wave (11 ms)
- Shocks contactor closed: 15 Gn for 1/2 sine wave (11 ms)
- Dimensions:
- Height: 170 mm
- Width: 163.5 mm
- Depth: 171 mm
- Net Weight: 3.83 kg